OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90556
PWS Name: TRIANGLE LAKE HIGH/ELEM SD 90
 
Who Was Contacted and Phone: Bob
Contact Date: 12/14/2005
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Exceeded copper AL again DETAILS: Bob called because he couldnt get a hold of Karen K or John P and he has a board meeting this evening. He just got the lead and copper results back. I walked him through the 90th percentile calculation over the phone. It looks like he exceeded the level for copper, but not lead. He said they are already practicing corrosion control. He wasnt sure what pH they were running it at, he will ask the operator. The minimum is set at 7.2. I suggested that the operator take daily pH readings for a couple weeks to see if they are getting a lot of fluccuation. I suggested that a re-evaluation of their treatment process may be necessary, but that he should talk to Karen or John about specifics. I directed him to the copper health effects sheet, and we discussed precautions to take, such as flushing the lines out before drinking. ACTION NEEDED: Karen or John will work with operator on resolving the issue.


More information for this water system: SDWIS ID 700
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login