OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05730
PWS Name: GH2O INC
 
Who Was Contacted and Phone: Bud Garland
Contact Date: 01/23/2006
Contacted By: BURNETT, GARY (DWP)
Contact Method/Location: Field
 
Assistance Type: BOIL WATER
Reasons: Coliform
N/A
 
Details: SUMMARY: Boil water warning rescinded effective 4 pm 1/24. DETAILS: We inspected the system and collected 6 coliforms samples. One sample at each of the 2 supply wells, and 4 from the distribution system. On 1/24 the lab reported that the sample collected at the old well was TC+. The well is used very little in the winter but may have been the cause of the fecal violation. After collecting samples on 1/23 4 oz of calcium hypochlorite was placed in the reservoir. Pedro Zabala (Hines) measured a residual of 0.3 mg/l chlorine on 1/24. ACTION NEEDED: The old well has been shut off until coliform samples indicate the well is free of coliform. Five routine samples to be collected in February.


More information for this water system: SDWIS ID 2484
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login