OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Bob Cochran
Contact Date: 03/08/2006
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: VOC detect in coal-tar lined reservoir DETAILS: Bob contacted me via email that they had done a VOC test on the coal-tar lined Reservoir #1, based on my recommendation after a sanitary survey (they didnt think it had ever been done). Results showed a very small detect of total xylenes (0.00077 ppm vs an MCL of 10, which is << 4 orders of magnitude). Also a detect of PCE was detected at an expected level given levels in their sources. Since coal tar can be more volatile in warmer temperature, I told bob to take another VOC sample this summer. If detections are significant, they will have to do a total of 4 quarters and we will decide from there what to do. Removing coal tar lining is recommended of course. Dave Stone suggested that PAHs can also leach out of coal tar (benzo(a) pyrene, an SOC), but we havent required that testing in the past. ACTION NEEDED: await summertime results


More information for this water system: SDWIS ID 3298
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login