PWS ID: OR41 00287
PWS Name: EUGENE WATER & ELECTRIC BOARD
 
Who Was Contacted and Phone: Brian Rigwood, Mitch Postle
Contact Date: 06/23/2006
Contacted By: POTTS, JOHN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: TCR + bactis in June 2006 DETAILS: Brian has informed DHS of recent TC + bacti results collected at a dedicated sampling station at 2000 Grant St. A site inspection revealed a broken/leaking water line in the sampling station. The sampling station has been shut down and will be replaced next week. Chlorine residual was present at the time of all sample collections at that site. Repeat sample results were negative. Routines were collected at this site on June 12 and June 21. Sample results can be invalidated as per 333-061-0036 (5) (k) C. No MCL violation. Mitch Postle will submit letter to DWP reviewing the situation and requesting sample invalidation. ACTION NEEDED: Refer to DMCA for invalidation.for samples collected at 2000 Grant.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3886