OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 94237
PWS Name: EUGENE YACHT CLUB
 
Who Was Contacted and Phone: Jack Chase (541) 935-2844
Contact Date: 08/03/2006
Contacted By: PARMENTER, AMY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: 5 total coliform positive routine samples DETAILS: I received an alert for 5 positive total coliform routine samples taken on 7/26/06. I talked with Jack Chase on 8/3/06. He said that they had a greywater line from the clubhouse that had a leak. Jack said the greywater line only runs 1 foot away from the water line, but the water line doesnt appear to have leaks, so he thinks maybe the greywater traveled to the wells. After the leak was repaired, they took 5 special samples on 8/1/06 and they all came back positive for total coliform, but the operators had not shocked/flushed the system. I advised them to shock/flush the system (both wells) using the procedure I mailed them in June or by hiring a well driller. I told them to wait a week after flushing before they take another sample to make sure the chlorine is gone, or to purchase a DPD-type chlorine test kit to verify the absence of chlorine if they want to take the samples sooner. I told them to take 5 routine samples during the month of August. I told them to keep the public notice posted until the problem is resolved and to mail me a copy. I asked them to call me with the results of the routine samples. ACTION NEEDED: Await results of the 2nd round of 5 routine samples.


More information for this water system: SDWIS ID 1666
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login