OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00362
PWS Name: HAINES, CITY OF
 
Who Was Contacted and Phone: Bruce Litke (541) 856-3366
Contact Date: 08/31/2006
Contacted By: GOSS, BILL (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: TC positive Alert Response DETAILS: 8/2/06-Routine monthly sample tests positive TC. 8/8/06-Four repeats samples were collected, all 4 were TC positive. 8-10-06 spoke with Bruce and Rena regarding disinfection methods. A new screen was installed over the top of the well casing to prevent animal intrusions. 8/14, 8/17 samples collected from the wellhead tested TC positive. System began using their backup well (Olson St) starting about August 15. 8-22-06- Bruce chlorinated the school well using two calcium hypochlorite biscuits and one gallon of 12.5% sodium hypochlorite. The well sat unused for four days, then was pumped. 8/25/06 - I mailed a public notice for the August MCI violation to the City with distribution instructions. 8-28-06 - Bruce collected a coliform sample at the school well and it tested TC positive. 8-31-06 Made a site visit. Collected colifrom samples at both wellheads, and at City Hall. Recommended opening the hydrant near the school well and flushing the well thoroughly. 9-1-06 Received results of coliform samples. Olson St well -TC/FC absent ACTION NEEDED: PWS to distribute public notice, collect five routine samples in September.


More information for this water system: SDWIS ID 3727
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login