OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00285
PWS Name: VILLAGE AT SEAVEY LOOP
 
Who Was Contacted and Phone: Pamela Stolsig (541) 484-4512
Contact Date: 11/01/2006
Contacted By: PARMENTER, AMY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: VIOLATION RESPONSE
Reasons: Operations
N/A
 
Details: SUMMARY: Chlorine residual level is 0 DETAILS: I received an alert for 0 chlorine residual. I spoke with Pamela on 11/1/06 who called the lab that does the sampling and lab said the residual was non-detectable. Pamela said they are only checking the chlorine residual once per week and that she has new managers that arent familiar with proper operations. I told her to bump the chlorine up so that she can detect a residual of at least 0.2 mg/L and to test and record the residual daily. I also told her Id send her a copy of the 2004 Sanitary Survey with a letter explaining the chlorine requirements so that she could share it with her managers. ACTION NEEDED: Send Pamela a letter and copy of Sanitary Survey.


More information for this water system: SDWIS ID 3291
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login