Details: SUMMARY: CT data reporting equipment failure DETAILS: John called Monday morning to report that the wind storm took out their CT structure on Thursday night. This is where they have continuous chlorine residual readings, temperature, and pH for CT compliance. Trees fell, bringing power lines down, particularly in the area of the CT structure. They could not go near it because of live wires. John Wesely was off on Friday (fixing the roof on his house), and no one called him or took grab sample measurements every 4 hours. The chlorine analyzer was working at headworks and shows no disruption in operation, and the daily checks at the inlet to the first reservoir (downstream of 1st user and CT station) were at their target of 1.3 ppm chlorine. Since this was a monitoring and reporting problem, not a water quality problem, I told John that it would be a violation requiring a Tier 3 public notice, not Tier 2. ACTION NEEDED: He will write up a letter explaining the situation and providing the data from headworks. He will report the violation in the 2006 CCR. Meanwhile they are considering ways to make sure this doesn’t happen again, like providing a propane generator at the CT station, or having an alternate site for grab measurements.


More information for this water system: SDWIS ID 3873
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login