OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00025
PWS Name: HAFEZ WATER SYSTEM
 
Who Was Contacted and Phone: Dan Daugherty, David Alford (541) 967-8633
Contact Date: 12/28/2006
Contacted By: POTTS, JOHN (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
None
 
Details: SUMMARY: Coliform positive bacteria sample results chlorine residual problems DETAILS: System had MCL Coliform problems in Nov 2006, 4 TC+ results. I visited the system Dec 15, 06 to evaluate the problem. The new Stenner chlorine injection pump is working, however no free chlorine residual is being maintained out in the system. I suggested that they raise the chlorine dosage until he maintains a free chlorine residual. He probably has not achieved breakpoint chlorination yet. He can adjust the chlorine to water ratio in the solution tank incrementally. Currently the ratio of 12.5 percent chlorine to 15 gallons of water. I also recommended that he sample for total chlorine residual to see how much chlorine is combined. I discussed their interest in installing a new reservoir for chlorine contact time to replace the existing 1000 gallon hydro pneumatic tank. They are proposing to install a 5000 gallon plastic reservoir in a yet to be constructed building near the existing well and chlorination building. I encouraged them to first conduct raw water sampling for at least six months with a 12 month sampling schedule more desirable in order to determine raw water quality year round before adding a new reservoir as it is uncertain of the coliform problems are source related or not . I sent a report to the system outlining my recommendations. ACTION NEEDED: None


More information for this water system: SDWIS ID 3217
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login