OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00025
PWS Name: HAFEZ WATER SYSTEM
 
Who Was Contacted and Phone: Dan Dougherty (541) 926-6026
Contact Date: 11/16/2006
Contacted By: HOY, DEBORAH (LINN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Chlorine
 
Details: SUMMARY: Responded to alert for pos. test result for coliform and for an ND chlorine residual received by DHS on 11/14/06 and by Linn County on 11/15/06 DETAILS: Routine taken on 11/8/06 at 1820 Hafez Lane outside tap (routine no. 1) was positive for total coliform. Operator was notified of the positive test on 11/15/06 because the contact person, David Alford, has been out of town and all messages went to Mr. Alford’s voicemail. Operator reports that the chlorinator went out 1.5 to 2 weeks ago. Linn County received the chlorine residual level alert showing 0.0 ppm in the system on 11/15/06. System has not been chlorinating since that time. Operator just received the part needed for repairs on 11/14/06 and has not had a chance to repair it. System is chlorinating for residual maintenance because of build-up in the distribution system. Operator says that he has not had time to take 4 repeats. I requested that he have the lab take the repeats ASAP and that he hire a company to repair the chlorinator ASAP or do it himself ASAP. After reviewing SDWIS I discovered that the system has had many chlorine residual readings of 0.0 or 0.1 ppm in the past year. This is our first chlorine residual ND alert. ACTION NEEDED: Follow up on 11/17/06 to ensure that repeats have been taken and that the chlorinator is back on line. Talk to water system about chlorine residual history and discuss using the circuit rider for help in maintaining the residual.


More information for this water system: SDWIS ID 3217
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login