OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 06138
PWS Name: DIAMOND RIDGE SUBDIVISION
 
Who Was Contacted and Phone: Patti Smith (541) 343-6108
Contact Date: 02/28/2007
Contacted By: PARMENTER, AMY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Total coliform positive routine sample and 4 negative repeats DETAILS: Casey Lyon, Russ Kazmierczak, and I took a routine coliform sample during my Sanitary Survey on 2/27/07. I was notified by the lab that the sample came out positive. The system chlorinates but there was no chlorine present in the sample. I spoke with Patti Smith, who spoke with her contact at Rainbow Pump, and they thought the sample might have been positive because the tap was a frost-free type. She said Rainbow Pump tested chlorine in other parts of the system and it was present however the chlorine pump needed to be primed. She took the 4 repeat samples and they came out negative for coliform and did have chlorine residuals. I instructed Patti to take 5 follow-up routine samples in March. ACTION NEEDED: Await results of the 5 routine samples.


More information for this water system: SDWIS ID 4962
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login