PWS ID: OR41 00252
PWS Name: DAYTON, CITY OF
 
Who Was Contacted and Phone: Gary Vanderveen
Contact Date: 09/14/2007
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: Coliform
N/A
 
Details: SUMMARY: boil response DETAILS: Dayton is on a boil alert. Pete handled in on Friday. He asked me about it before I left on Friday and I believe he did the correct thing. Positive EColi followed by a positive TC repeat (at a different site). Anyway Gary at the county called and said they are handling it. He will inspect the sample sites/plan today. Also, try to increase chlorine residual. They are going to add chlorine to the reservoir. Calculated out that 30 gallons of 12.5 % into a 1.5mg res will give them 2.5 ppm. Gary said that city added 15 gallons earlier and only got 0.5 ppm. He will ask them to add 15 gallons of 12.5% again. This will flush through system. They will try to up the chlorine feed system to always keep a 0.5 ppm residual. Normal working residuals in the system are much lower than that. ACTION NEEDED: Gary to keep working with system.


More information for this water system: SDWIS ID 4135
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login