OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95069
PWS Name: JASPER MOUNTAIN CENTER
 
Who Was Contacted and Phone: Chuck Davis (541) 744-3730
Contact Date: 01/03/2007
Contacted By: LYON, CASEY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Arsenic
Arsenic
 
Details: SUMMARY: alert-Arsenic DETAILS: Spoke with Chuck Davis today about recent Arsenic samples above MCL. The sample taken 12/7/07 with a result of .0223 mg/L was a raw water sample taken with the inorganic suite. The sample taken 12/26/07 with a result of .0193 mg/L was taken after central treatment and was still above the MCL. Chuck stated that the Arsenic treatment is not working properly because the raw water pH is 9.2 and this Arsenic treatment works best at around a pH of 7. He is installing a Muriatic acid feed system to bring the pH down and this will hopefully bring the As levels below the MCL. I have changed their As sampling schedule to quarterly. I notifyed him we will do a yearly average once 4 quarterly samples results are in. ACTION NEEDED: Take three more quarterly samples to determine yearly Arsenic average.


More information for this water system: SDWIS ID 4533
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login