PWS ID: OR41 01305
PWS Name: AVION WC - WHYCHUS CREEK
 
Who Was Contacted and Phone: Ron Remund (541) 549-6261
Contact Date: 12/04/2007
Contacted By: FREUND, JEFF (DESCHUTES COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Routine Sample Positive for TC and E.coli DETAILS: November routine sample positive for tc and e-coli. 5 repeats showed 2 e-coli and 3 tc+. Discussed with Ron throughout the next several weeks and faxed PN boil water notices. PN posted 12/4 and again 12/14. System hired Butch Rogers to help find problem and fix. Affected well seemed to be #5. Well and reservoir was chlorinated several times but resamples continued to show presence of e-coli bacteria. System eventually installed chlorinator on or about 12/16/07. Contact time is achieved in reservoir and distribution chlorine residual between .1-1.0ppm. PN to inform water ok to use posted 12/1807.Spoke with Ron 1/2/08 and chlorine injection point has been moved to discharge of well #5. Discussed the need for 5 routines this month as well as weekly raw samples from well 5 for the month. ACTION NEEDED: Take 5 routines in January plus weekly special samples from source to confirm no more contamination. Cannot discontinue chlorination until 4 weekly raw samples for #5 absent. Continue to take and record residual chlorine in distribution system. System is trying to get one or more of the other existing wells on line as backup sources. System needs plan review for new reservoir and wells 3, 4, 5. System also needs new operator (distribution 1 operator), cross connection program with enabling authority, coliform sampling plan and ERP.
 
Associated Alerts: COLI4858 - 12/03/2007 - COLIFORM (TCR) , E. COLI

COLI4858 - 12/03/2007 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 2368
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login