OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00586
PWS Name: ODELL WATER COMPANY
 
Who Was Contacted and Phone: Phil Davis (541) 354-1885
Contact Date: 12/14/2007
Contacted By: FETKENHOUR, JEFF (HOOD RIVER COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
N/A
 
Details: SUMMARY: Two Nitrate Samples Exceed MCL DETAILS: The Hood River County Health Department received an alert by fax on Thursday 12/13/07 @ 9:05 AM for the OWC in response to 2 Nitrate sample results which exceeded the action level of 0.5 MCL. Sample Id 0731814PD, collected on 11/14/07, has a nitrate concentration of 8 mg/L-- sample ID 0724009PD, collected on 8/28/07, had a nitrate concentration of 8.4 mg/L. A second alert was received on Thursday 12/20/07 @ 9:05 AM for the Odell Water Company in response to an earlier Nitrate sample result which also exceeded the action level of 0.5 MCL. Sample ID 0716424PD, collected on 6/13/17, has a nitrate concentration of 8.4 mg/L. HRCHD discussed these results with Phil Davis the week of 12/3/07 and acknowledged that the action level would be triggered, but that the trend of increasing nitrate concentrations appears to have plateaued. OWC is recognized by the DHS SWP online database for maintaining nitrate samples reliable and consistently below the MCL. Subsequently, the sampling schedule expectation is to comply with yearly nitrate sampling-- quarterly nitrate sampling is still not expected or required for the OWC. OWC has agreed nonetheless to increase the number of samples collected during the year to provide additional monitoring. ACTION NEEDED: HRCHD has initiated dialogue with the DWP Springfield office to begin a surveillance effort to identify likely contributory point sources that may be amenable to remediation to mitigate further increase in the nitrate concentration. If nitrate values exceed the MCL, an adjustment to the chemical schedule will be imposed.
 
Associated Alerts: CHEM2721 - 12/13/2007 - NITRATE

CHEM2721 - 12/13/2007 - NITRATE



More information for this water system: SDWIS ID 3373
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login