OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00452
PWS Name: LAFAYETTE, CITY OF
 
Who Was Contacted and Phone: Jim Anderson (503) 437-0401
Contact Date: 04/02/2008
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Chlorine
CL
 
Details: SUMMARY: High chlorine residual DETAILS: Jim Anderson called today with a problem with high chlorine residual. He said that on Monday March 31st a piece broke on their main chlorinator. The part will take one and a half weeks to get in. He replaced the chlorinator with a spare chlorinator at 2.5 gph, which he said was smaller than their normal chlorinator. He set the speed and stroke at about 50%. On Tuesday morning the chlorine residual was 0.82 ppm. By Tuesday afternoon the residual in the same location was 4.09 ppm. He changed the feed pump setting to 25%, but today the reading is 5.2 ppm. He shut off the chlorinator to try to dilute the chlorine concentration in the tank. After some confusion, it was determined that this is an acceptable practice as long as someone is there checking the effluent chlorine concentration. They need disinfection, not just residual maintenance. Calculations determined that at a 50% setting using 12.5% chlorine, that would be a concentration of 8.3 ppm. I called HBH to see if they could help with the situation, and they will try to send someone out. Jim was planning to stay into the evening until he had it figured out. ACTION NEEDED: Water system will need to do a Tier 2 public notice within 30 days
 
Associated Alerts: N/A - -



More information for this water system: SDWIS ID 4296
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login