OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95084
PWS Name: JASPER WOOD PRODUCTS
 
Who Was Contacted and Phone: Everett Blilie (541) 988-1127
Contact Date: 06/13/2008
Contacted By: KAZMIERCZAK, RUSSELL (DWP)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: Coliform
Coliform
 
Details: SUMMARY: 5 routine samples collected on 6/11/08 were TC+ and one was confirmed EC+. DETAILS: 5 repeat samples collected on 6/11/08 were TC+ and one was confirmed EC+. Called water system contact, Everett Blilie, on June 13, 2008 regarding confirmed EC+. He indicated that they are in the process of correcting two possible causes, an old leaking galvanized pressure tank and a small 3/4 inch water line connected to a sink. He thinks the air from re-pressurization of the tank or stagnant water in the sink line is draining back into the distribution system. The pressure tank is being replaced and a backflow/check valve is being installed on the water line. He also indicated that they have posted Boil Water notices at all the drinking water sources and the system is also providing bottled water to employees. After the tank and check valve is replaced the water system is going shock chlorinate the system again and then 5 more routine samples will be collected. ACTION NEEDED: After the possible causes are addressed, the water system will shock chlorinate and collect five routine samples to verify that corrective action resolved the problem.


More information for this water system: SDWIS ID 4569
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login