OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00917
PWS Name: VALE, CITY OF
 
Who Was Contacted and Phone: Mike Holladay, P.E. (208) 642-3304
Contact Date: 07/02/2008
Contacted By: BURNETT, GARY (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
Arsenic
 
Details: SUMMARY: Reviewed status of water treatment equipment because nitrate result is 6.57 mg/l DETAILS: I talked to both Les Bertalotto with the City and Mike Holladay consulting engineer. The ion-exchange treatment unit reduces both arsenic and nitrate but there had been some problems in February-March 2008 which caused the treatment unit to be shut off for several weeks. The water has elevated levels of TOC which binds with the resin and drastically shortens the time between resin regeneration. Design parameter was 600,000 gallons treated before regeneration required, but the binding problem reduced the amount to 300,000 gallons and therefore the wastewater system could not handle the increase in waste. The treatment system is now working but does not reduce arsenic or nitrate as much as expected. Mike Holladay feels the arsenic level is below 10 mg/l and the City took an arsenic sample June 28. ACTION NEEDED: Les Bertalotto and Mike Holladay are meeting with EPA, design engineers, and treatment equipment suppliers in Columbus Ohio on July 14 to review methods of improving treatment efficiency. Mike Holladay will notify DWP of conclusions. An arsenic sample was taken June 28 and that result will be reported as soon as available.


More information for this water system: SDWIS ID 3802
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login