PWS Name: HIDDEN VALLEY WATER SYSTEM
 
Who Was Contacted and Phone: Marti Palmer (541) 451-4499
Contact Date: 04/17/2008
Contacted By: HOY, DEBORAH (LINN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Coliform
 
Details: SUMMARY: Alert on 4/17/08 for 3 positive repeat coliform bacteria tests sampled 4/15/08. DETAILS: Marti has met with Stutzman Services regarding the chlorinator not working properly. Stutzman worked on it and apparently it is fixed now. Discussed posting/sending a Tier 2 public notice to residents. She will send a copy to Linn Co. EH. Marti is using a pool test kit for chlorine residuals and has got varied residual results from 0.1-0.5ppm. I told her that she needs to use an approved test kit and reagent and told her about the HACH website. I informed Marti about the minimum chlorine residual of 0.2 ppm and recommended that she maintain a chlorine residual between 0.3 -0.5. System is not using NSF approved chlorine. I told her to use the approved NSF chlorine that is available from Stutzman Services. Marti mentioned that a pit was discovered ~30 from the water system well. She will have her well driller look at it and discuss it with the land owner. Informed Mari of the required 5 routines in May. We discussed the need for a Water System Survey and set a date. ACTION NEEDED: Wait for results of 5 routines in May.
 
Associated Alerts: COLI5155 - 04/17/2008 - COLIFORM (TCR)

COLI5155 - 04/17/2008 - COLIFORM (TCR)

COLI5155 - 04/17/2008 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4313
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login