OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05117
PWS Name: DARK HOLLOW WATER ASSOCIATION
 
Who Was Contacted and Phone: Jerry Manuel (541) 779-9774
Contact Date: 04/02/2008
Contacted By: HOUGH, DANIEL (JACKSON COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Routine samples collected on 3/31/08 and 4/01/08 tested positive for Total Coliform DETAILS: 4/2/08 - I left Jerry a voice mail requesting that he call me back. 5/01/08 - Left Jerry another voice mail requesting that he call me back. 5/13/08 - I sent Jerry the attached letter stating that four repeat samples within 24 hours must be taken. 5/16/08 - Jerry called me. We agreed that their 10,000 gallon storage tank will likely always have a problem without a continuous chlorine residual. I recommended that Jerry talk to the water board and pursue the instillation of continuous chlorination immediately. Jerry will do that and get back to me next week. Jerry also collected two special samples (3255 Carriage Dr. and 3250 Darrel Dr.) 5/22/08 - Both special samples collected passed. I called Jerry and he notified me that they are going to have continuous chlorination installed. I asked Jerry to call Scott Curry to initiate the plan review process. ACTION NEEDED: Plans need to be submitted for the proposed continuous chlorination system.
 
Associated Alerts: COLI5123 - 04/02/2008 - COLIFORM, TOTAL (TCR)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 174