OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90556
PWS Name: TRIANGLE LAKE HIGH/ELEM SD 90
 
Who Was Contacted and Phone: Jeff Richardson (541) 925-3262 ext. 124
Contact Date: 09/10/2008
Contacted By: PARRY, BETSY (REGION 2)
Contact Method/Location: Field
 
Assistance Type: SURVEY/DEFICIENCY FOLLOW-UP
Reasons: Lead or Copper
Operations
 
Details: SUMMARY: checked their pH meter as follow up to WSS DETAILS: During the WSS survey July 2, we found that our agency pH meter was reading a bit lower than Jeffs. His corrosion control program requires that the waters pH remain at 7.2 or higher. Jeff has replaced the battery and calibrated his meter, and we tested it again today. I still got 7.2 on our agency meter-- he got 7.4. Jeffs next step is to order new calibration buffers (his are expired) or perhaps just order a new pH meter. Also, he showed me the bleach he has been using (Pure Bright) that meets NSF standard 60 (Jeff researched it on the NSF website and also placed a phone call to the manufacturer) even though the NSF logo does not appear on the label. ACTION NEEDED: Check back again after Jeff has gotten either a new pH meter or better buffers to calibrate the one he has. Added photos of his current bleach supply (bottle) to the recent survey photos on file, labeled with todays date.


More information for this water system: SDWIS ID 700
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login