OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrick Yates (503) 969-6449
Contact Date: 10/10/2008
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: Tetrachloroethylene detect from well 6 DETAILS: I spoke with Derrick about the Tetrachloroethylene(PCE) detection of 4.09 ppb from the 7/15/08 sample. MCL is 5 ppb, and the Running Annual Average from the last 4 quarterly samples is 4 ppb. Since the result is close to the MCL, Fairview will continue quarterly sampling for PCE. ACTION NEEDED: Fairview to continue quarterly monitoring for PCE at the Entry Point for Well 6.
 
Associated Alerts: CHEM3174 - 10/09/2008 - TETRACHLOROETHYLENE



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3298