OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05737
PWS Name: BERNDT CREEK WATER CORP
 
Who Was Contacted and Phone: Martin Van Dyken (503) 429-2505
Contact Date: 11/05/2008
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
VOC
 
Details: SUMMARY: Toluene Detection of 0.006 mg/l on 09/03/08 DETAILS: A routine annual VOC sample taken 09/03/08 indicated the presence of toluene at 0.006 mg/l (Toluene MCL is 1 mg/l). I contacted Martin who wondered if it could have been due to recoating the inside of a tank on 08/17/08 with Sherwin Williams Dura-Plate UHS (an NSF Std 61 product). I contacted a representative from Sherwin Williams who said that the Dura-Plate UHS does not contain toluene and would not off-gas toluene. Martin also thought that the source could have been from when they repainted the outside of the tank using Hamerite spray paint. I told him it is possible, but that we needed more sample results to confirm if the problem is more persistent. I told him that I would send some information regarding the health effects of Toluene exposure and that he should begin quarterly sampling. ACTION NEEDED: System to begin a series of quarterly entry point sampling for Toluene for 4 consecutive quarters, with the first sample to be taken before 12/31/08. Results will dictate future monitoring and/or treatment requirements. System is to report any detections in the annual consumer confidence report.
 
Associated Alerts: CHEM3233 - 11/05/2008 - TOLUENE



More information for this water system: SDWIS ID 2056
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login