OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00067
PWS Name: AURORA, CITY OF
 
Who Was Contacted and Phone: Bob Southard (503) 678-1035
Contact Date: 11/06/2008
Contacted By: BAIRD, GREGG (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Routine collected 11/4/08 +TC and e.coli DETAILS: Received info that system had a +TC and +e.coli routine sample-- called Marion Co Health and left msg-- called the system at 10:30am and left a message. Heard back from Bob Southard a little bit later and he said he was aware of the positives. He indicated that he only had one sample bottle available, so he would collect one repeat sample today (Thursday) and take in to the lab, pick up some more bottles, and then collect more samples Friday morning and take them in to the lab. Bob said he would request that the lab test these same-day so we could have all the repeat results by Friday afternoon. He indicated that it was raining heavily during the initial routine sampling and he suspects it might have contaminated the sample. The cause of having no chlorine residual is also being investigated. ACTION NEEDED: Will continue to monitor the situation and wait to see results of the repeat samples. If all repeats are absent of coliform, then operator will need to collect 5 temp routines in December. If any repeat is +TC or +e.coli, then further action will be required including public notice.
 
Associated Alerts: COLI5838 - 11/06/2008 - COLIFORM (TCR) , E. COLI

COLI5838 - 11/06/2008 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3233
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login