OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00018
PWS Name: SCRAVEL HILL WATER CO-OP
 
Who Was Contacted and Phone: Monty Torgeson (541) 926-1974
Contact Date: 08/05/2008
Contacted By: HOY, DEBORAH (LINN COUNTY)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Lead or Copper
Lead/Copper
 
Details: SUMMARY: Recent L & C results. DETAILS: Monty called to report 2 samples came back positive from the most recent round of L & C monitoring this summer. One result was 0.016 ppm and another was 0.010 ppm lead. All other sites tested ND. All copper testing was ND according to Monty. I calculated the 90th percentile for lead as 13 ppb (0.013 ppm) which is below the action level of 15 ppb. I asked Monty if he followed the L & C sampling site plan and he said he wasnt aware of the plan. He informed me that he is only a volunteer and doesnt have time for this. I suggested that he find a volunteer who does have time to operate the system or contract with a certified operator. I found the most recent plan in Linn County records that Monty prepared in Oct. 1997. I will send him a copy. If Monty did not follow the plan I will ask him to make an authorized/certified change to the plan (141A) or correct the monitoring that was just completed by contacting me regarding the steps to take. Monty states that the corrosion control system is operating fine. ACTION NEEDED: Wait for Monty to call if he did not follow sampling site plan for L & C.


More information for this water system: SDWIS ID 3213
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login