OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00012
PWS Name: ALBANY, CITY OF
 
Who Was Contacted and Phone: Jim Young (541) 917-7609
Contact Date: 11/17/2008
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: Tetrachloroethylene Detects in Distribution 11/7/2008. DETAILS: Jim contact me on 11/12/2008 regarding a detection of tetrachloroethylene (PCE) in the distribution system. Two distribution samples were collected for compliance with Stage 2 DBPR, however, the lab analyzed the samples for other contaminants at the same time. As a result, a detect of PCE was found at a locations in N. Albany. The result was 0.0076 mg/L and was above the MCL of 0.0050 mg/L. The other sample was ND for PCE. Jim is not sure what would cause this detect, however, he suspects some builders may have used a cleaning agent on valves installed in a new development nearby. In the meantime, while these samples are not required by the SDWA (only EP samples required), quarterly samples are needed to determine compliance with MCLs and public notice requirements. Jim is collecting confirmation samples and will notify us of the results. ACTION NEEDED: Await results of quarterly monitoring and confirmation samples. Public notice and CCR notification requirements will be based on those results.


More information for this water system: SDWIS ID 3872
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login