OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Bob Cochran (503) 665-9320
Contact Date: 05/22/2009
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
SOCs
 
Details: SUMMARY: Response to VOC/SOC detections at well 6 DETAILS: Spoke to Bob regarding chemical detections of Tetrachloroethylene (PCE), Trichloroethylene (TCE), and Ethylene Dibromide (EDB) at well 6. Well 6 currently off-line. Second quarter data showed PCE detect at 0.00531 mg/l (MCL 0.005), EDB detect at 0.0000506 mg/l (MCL 0.00005), and TCE detect at 0.00068 (MCL 0.005). Discussed compliance with MCL determined by a running annual average of 4 quarterly samples. Stated that if average > MCL, and well 6 is on-line, an MCL violation would occur, and Fairview would need to post tier II public notice. Also I indicated that City will need to report any detections of regulated contaminants at active wells in CCR. Bob stated that City only plans to use well 6 this summer as a last resort. Feels they can meet there summer demand. ACTION NEEDED: Fairview to continue quarterly monitoring for PCE, TCE, and EDB at well 6. Fairview to contact DWP before placing well 6 on-line. DWP to provide support as necessary.
 
Associated Alerts: CHEM3517 - 05/21/2009 - ETHYLENE DIBROMIDE, TETRACHLOROETHYLENE , TRICHLOROETHYLENE

CHEM3517 - 05/21/2009 - ETHYLENE DIBROMIDE, TETRACHLOROETHYLENE , TRICHLOROETHYLENE

CHEM3517 - 05/21/2009 - ETHYLENE DIBROMIDE, TETRACHLOROETHYLENE , TRICHLOROETHYLENE



More information for this water system: SDWIS ID 3298
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login