OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91810
PWS Name: FERN RIDGE MIDDLE SCHOOL
 
Who Was Contacted and Phone: Jeff Thiessen (541) 935-2253
Contact Date: 04/09/2009
Contacted By: CHAPEK, KATRINKA (LANE COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: LCR excursion DETAILS: Left message for Jeff. Explained that hi ph dropped below the minimum 3 times last month and I wanted to find out if he had any ideas as to why. Also mentioned that the EPA chemist, Michael Schock had encouraged Jeff to look into aeration treatment - wanted to find out the status on that also. Jeff replied back with the following email. I am finding caustic soda a sensitive corrosion control agent. Any disruption in the system ie: chemical pumps loosing its prime, unusual water volumes, chlorine levels-- results in a wild swing in ph levels. Because of the sensitive nature of caustic soda I try to keep the hp readings as close go minimum as possible which at times drops below set levels. If I maintain caustic soda levels higher to provide a larger buffer zone I receive complaints of slimy water. Using aeration is still an option but would require a capital outlay for the district which they are not able to do right now. ACTION NEEDED: Continue to monitor until funding allows other treatment possibilities.
 
Associated Alerts: LCRE9574 - 04/08/2009 -



More information for this water system: SDWIS ID 1033
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login