OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91671
PWS Name: DIXIE ELEMENTARY SD 509J
 
Who Was Contacted and Phone: Paul Jennison/Kim Patton/Tim Trivett (541) 757-5877
Contact Date: 02/25/2010
Contacted By: POTTS, JOHN (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Technical Assistance for Lead Action Level Exceedance DETAILS: System requested HBH assistance for options for complying with LCR due to lead action level exceedence (0.0218 mgl) in samples collected 8/21/09. It appears that classroom #1 sink faucet is the only site that exceeded the action levels in the round of samples. Previous sample results indicated elevated lead levels at individual sites. Water Quality Parameters and lead source water samples have been collected. The pH levels are very low, 6.2, and alkalinity is relatively high at 96 mgl. The sink faucet in classroom #1 was changed out in 2007 to a Chicago faucet, which is considered no/low lead type. I met with Paul, Kim and Tim on Feb 23 to review results evaluating previous plumbing modifications done, facility usage, and discussed possible corrective measures. I also met Paul and Tim at the site on Feb 26 to inspect piping and fixtures. I talked with Alyson Reynolds, Linn Co EHD, regarding compliance options and preparation of a proposed for her review and approval. ACTION NEEDED: Complete written proposal for Linn Co and determine any further action based upon reply.


More information for this water system: SDWIS ID 979
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login