OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93817
PWS Name: USFS PARADISE CAMPGRD/HELIPORT
 
Who Was Contacted and Phone: Nic Fedderhoff (541) 231-1811
Contact Date: 08/08/2010
Contacted By: BIRDSALL, JEFF (LANE COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Respond tp Alert for Total Coliform DETAILS: Five routine samples positive, discussed with Dave Sanders with the USFS (Guy Cohoon not in) and Nic Fedderhoff. Dave says the storage holding tank was cleaned in July 19,2010. Nic says the system was recently shocked on two occasions, once in mid-June 2010 and again the first week of July. He says the well does not have a shock spout so therefore he shocked the storage holding tank for twenty-four hours at 100 ppm chlorine. He held the chlorinated water in the tank and distribution and drain for twenty-four hours on each occasion. He says there is one section of like that is 1/4 mile in length that runs from the water source to the storage holding tank that is not easily accessible and therefore they have not been able to shock the well. The Tier 2 Notice has been updated and they will fax me a copy. They will continue with corrective action in order to attempt to solve the problem. ACTION NEEDED: Continue corrective action to determine the cause of the total coliform positive samples and correct it.
 
Associated Alerts: COLI7994 - 08/04/2010 - COLIFORM (TCR)

COLI7994 - 08/04/2010 - COLIFORM (TCR)

COLI7994 - 08/04/2010 - COLIFORM (TCR)

COLI7994 - 08/04/2010 - COLIFORM (TCR)

COLI7994 - 08/04/2010 - COLIFORM (TCR)



More information for this water system: SDWIS ID 1467
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login