Who Was Contacted and Phone: John Higgins (541) 396-2115 ext. 209
Contact Date: 01/12/2011
Contacted By: MACPHERSON, JAMES (REGION 2)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Chlorine
None
 
Details: SUMMARY: Chlorine residual drop at first user DETAILS: Chlorine at the first user (treatment plant lab) dropped below 0.4 mg/L, causing failure to meet CT. The chlorine concentration can be measured at the stainless steel (SS) tank outlet, to address rxn losses in the pipe going into the lab. Also, some recirculation of SS tank flow can go back to concrete clearwell (the concrete and SS together are effectively the clearwell) as long as return flow isnt at the outlet of the concrete clearwell. Or the tank level could be dropped, as far as the level used in the tracer study. Or the chlorine concentration could be increased. Or a combination of all the above could be used. ACTION NEEDED: Send e-mail to Coquille.


More information for this water system: SDWIS ID 3882
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login