OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01044
PWS Name: TIERRA LINDA ESTATES
 
Who Was Contacted and Phone: Dave Hackler (541) 567-6995
Contact Date: 01/14/2011
Contacted By: BAKER, AMY (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Nitrate
N/A
 
Details: SUMMARY: follow up to elevated nitrate alert DETAILS: System took a nitrate sample on November 17, 2010. The result was 5.48 mg/l for nitrate. Since the result is over 1/2 of the MCL - the system was placed on a quarterly schedule. The nitrate levels have gradually risen over the years. Schedule to be reevaluated after quarterly sampling is complete (through 3rd qtr 2011). System was also asked to get radionuclide sampling complete to be able to set the schedule. ACTION NEEDED: Take 3 quarterly nitrate samples in 2011 - (1st-2nd-3rd quarters). Rads: 2 quarters of Gross Alpha, 1 quarter Radium 226/228, and Uranium - 3 quarters.
 
Associated Alerts: CHEM4686 - 01/12/2011 - NITRATE , SODIUM

CHEM4686 - 01/12/2011 - NITRATE , SODIUM



More information for this water system: SDWIS ID 3810
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login