OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrrick Yates (503) 665-9320
Contact Date: 02/23/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: Response to 1st Qtr 2011 VOC Monitoring wells #5 and 6 DETAILS: Well #6 PCE detected at 0.00503 mg/L (MCL is 0.005), running annual average of last 4 quarters below MCL, discussed staying on quarterly frequency as values not reliably and consistly below MCL. TCE at well #6 detected at 0.00063 mg/L (MCL is 0.005). Continue annual during first quarter for TCE at #6, as reliably and consistently below MCL. Well #6 inactive since Dec 2008, but City wishes to continue monitoring in off chance well is needed. Well #5 remains in back up status, and PCE detected at 0.00244 mg/L or roughly half MCL. We discussed that since quarterly results in past showed results reliably and consistently below MCL, continue annually during 1st quarter as outlined in VOC rule. Derrick indicated DEQ study occurring regarding potential hospital laundrymat in area that could be contributer to VOC detections. ACTION NEEDED: Continue quarterly for PCE at well #6, annual for TCE at well #6, and PCE at well #5. DWP to continue to provide support to City with regards to organic detections at wells.
 
Associated Alerts: CHEM4763 - 02/22/2011 - TETRACHLOROETHYLENE , TRICHLOROETHYLENE

CHEM4763 - 02/22/2011 - TETRACHLOROETHYLENE , TRICHLOROETHYLENE

CHEM4763 - 02/22/2011 - TETRACHLOROETHYLENE , TRICHLOROETHYLENE



More information for this water system: SDWIS ID 3298
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login