OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05737
PWS Name: BERNDT CREEK WATER CORP
 
Who Was Contacted and Phone: Martin van Dyken (503) 429-2505
Contact Date: 05/25/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: Response to Toluene and Ethylbenzene detects DETAILS: I spoke to Martin about two May 4, 2011 detects. Toluene at 0.0007 mg/L and Ethylbenzene at 0.0005 mg/L (the detection limit). Given that we have now 4 consecutive qtrs of toluene, with a running annual average of 0.000525 mg/L, well below MCL of 1 mg/L, I indicated to Martin that frequency can be reduced to once annually, with next sample with 3rd quarter 2012 VOCs. Ethylbenzene detect is right at the detection limit, and that we already have 4 consecutive quarters of ethylbenzene (running annual average of 0.000125 mg/L), the annual variability of the compound has been established. Ethylbenzene to be monitored with VOC suite in 3rd qtr 2012. System has been working with DEQ to notify users in watershed about best management practices for fuel, household and home septic tanks to protect water source in Rock Creek Area, and has contacted forest companies to research spraying practices. ACTION NEEDED: Martin to monitor for VOCs annually during 3rd quarter beginning with 2012. Martin will mail out letters to residents in the watershed first week of June regarding household hazardous and septic waste management pracatices. DWP to continue to research potential sources of compounds through spraying or road application practices. DWP to continue to support Water system in understanding potential source of detects. Martin reports detects in Consumer Confidence Report.
 
Associated Alerts: CHEM4882 - 05/24/2011 - ETHYLBENZENE , TOLUENE

CHEM4882 - 05/24/2011 - ETHYLBENZENE , TOLUENE



More information for this water system: SDWIS ID 2056
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login