OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrick Yates (503) 665-9320
Contact Date: 05/19/2011
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: April 2011 PCE detect well #6 DETAILS: Derrick confirmed that Fairviews well #6 had a detect of 0.00478 mg/L tetrachloroethylene (PCE) on 4/8/11. MCL is 0.005 mg/L. Running average of last 4 quarters of data is 0.00458 mg/L. Well off-line since Dec 2008. System has no plans to use well #6, only during emergency situations. Monitoring kept up on well #6, simply to have current water quality data in the rare event well is needed. ACTION NEEDED: City to continue to monitor well #6 quarterly for PCE.
 
Associated Alerts: CHEM4883 - 05/27/2011 - TETRACHLOROETHYLENE