OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00869
PWS Name: THE DALLES, CITY OF
 
Who Was Contacted and Phone: Ken Rawson (541) 298-2248 ext. 5000
Contact Date: 06/23/2011
Contacted By: GOSS, BILL (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
N/A
 
Details: SUMMARY: Review of Tracer Study Results DETAILS: The 250,000 gallon clearwell is offline for maintenance, so only the 4.3 MG clearwell is in use, and a new tracer study is warranted. Ken sent the results of a tracer study conducted 6/21 - 22. The sampling at the clearwell outlet missed the tracer (fluoride) breakthrough, so a second tracer study will be conducted in a couple days. Recommended turning off the fluoride and waiting until it was non-detect at the clearwell outlet, then starting the study with a dosage of 0.7 mg/l and take measurements until 0.07 mg/l was achieved at the outlet. ACTION NEEDED: PWS to submit tracer study results.


More information for this water system: SDWIS ID 3916
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login