PWS ID: OR41 05246
PWS Name: PGE BEAVER GENERATING STATION
 
Who Was Contacted and Phone: Bob Reller (503) 728-7204
Contact Date: 04/09/2012
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
N/A
 
Details: SUMMARY: Pre-emptive do not drink notice DETAILS: Bob called to update me that PGE Beaver will be issuing a precautionary do not drink notice and placarding accordingly sinks and fountains around the plant in response to dropping chlorine residual readings in system. System will be providing bottled water to all employees. System residuals dropped from 1-1.2 mg/l to 0.2 mg/L in five days, due to high chlorine demand in their elevated tower and heavy use, and expected to drop more. Plant off since 4/5, with CTs being met at that time, and system going off water in elevated tower. I explained that system is required to maintain a detectable residual at all times in distribution and this notification is pre-emptive by the plant at this time. We discussed addressing causes of high chlorine demand in tower and system. System will need to follow Best Management Practices for treatment / disinfection interruptions to come off self-initiated do not drink notice. BMP forwarded to system. ACTION NEEDED: System will post notice and do not drink placards today (4/9), and work with DWP to lift restriction, and notify employees accordingly. DWP to support system to re-establish treatment and disinfection, ensure NTUs and CTs met with detectable residual throughout distribution and other necessary steps to lift pre-emptive notification. DWP to support system in addressing causes of high chlorine residual demand in elevated tower and system.


More information for this water system: SDWIS ID 4162
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login