OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01094
PWS Name: USFS TOKETEE RANGER STATION
 
Who Was Contacted and Phone: Michelle Bernard (541) 957-3401
Contact Date: 05/14/2012
Contacted By: KALISH, FRED (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Coliform
Operations
 
Details: SUMMARY: Repeat coliform sampling results DETAILS: Michelle called to discuss the fact that their repeat sampling from over the weekend resulted in positive coliforms in the distribution sample and ND in the wellhead sample. We discussed the requirement for corrective action (typically shock chlorination of well and distribution system) and MCL violation requiring Tier 2 public notice. We also discussed the requirement for 5 routine coliform samples in June. ACTION NEEDED: Wait for completion of followup testing after shock chlorination, and documentation of public notice.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3540