OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 94157
PWS Name: HAMLET QUICK-STOP
 
Who Was Contacted and Phone: Ludek Winkler (503) 738-0302
Contact Date: 06/15/2012
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Field
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
Operations
 
Details: SUMMARY: Stopped by to check in on operations and check turbidity DETAILS: I stopped in to check the filter effluent turbidity and see how things were going. The turbidity was measured to be 0.5 NTU and the chlorine residual was holding steady at around 0.7 - 0.8 mg/l. I explained that the turbidity should always be less than 1 NTU and to call our office if results were ever above that level. I let him know that he had reported 5 NTU, but he thought that he had not recorded the results accurately. ACTION NEEDED: Keep monitoring chlorine residuals and turbidity and keep DWP apprised of high turbidity or low chlorine residuals.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 2198