OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00949
PWS Name: WESTON, CITY OF
 
Who Was Contacted and Phone: Scott Spendlove (541) 566-3976
Contact Date: 07/28/2012
Contacted By: GOSS, BILL (DWP)
Contact Method/Location: Field
 
Assistance Type: BOIL WATER
Reasons: Coliform
N/A
 
Details: SUMMARY: Loss of Pressure Leads to Boil Order DETAILS: 7/28/12 – At approximately 6:10 am Saturday a landslide occurred that damaged a section of the transmission line that runs between the city’s well/reservoir and town. The reservoir did not drain completely before city staff arrived and closed the reservoir outlet valve, but 300,000 gallons or more likely flowed out through the broken line, washing soil and mud down into Pine Creek. A boil water warning was distributed later that day due to a loss of pressure in most areas of town. Some areas at the lowest elevations maintained a low positive pressure. A temporary intertie was established between the city system and Smith Frozen Foods, PWS #4190234, by connecting two fire hydrants. A potable water tanker was brought in so residents could fill water jugs, several portable toilets were placed throughout town, and a mobile shower unit was brought in. Pressure was restored throughout the city system by late Saturday evening, but the boil order remained in effect. ACTION NEEDED: City to complete repairs to transmission line, pressure test and flush, restore connection to distribution system, maintain chlorine residual in the interim, collect routine sample for August after chlorine residual is non-detectable.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3805