OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90416
PWS Name: GEORGIA-PACIFIC, WAUNA MILL
 
Who Was Contacted and Phone: Jeffery Sorensen (503) 455-3236
Contact Date: 04/26/2013
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SWTR
Operations
 
Details: SUMMARY: Operations DETAILS: I received a call from Jeff Sorensen regarding a brief spike in filter effluent turbidity. The spike ocurred at 11:33 AM on 4/26/13 and the turbidity was above 1.49 NTU for about 90 seconds, with a maximum spike of 1.56 NTU. There was no corresponding spike in the influent turbidity prior to the pressure filters, which comes from a sidestream of water that has been fully treated through a rapid rate plant, primarily for use as process water. Turbidity was back down to 0.09 NTU and the 4-hr compliance readings were all within normal ranges. They are still investigating the cause of the incident. Even at a 200 gpm max flow, 90 seconds above 1.49 NTU, would only amount to 300 gallons into a 50,000 gallon clearwell (25,000 gallon at lowest level), which would be about 0.6 - 1.2% of the available storage. Contact time is 132 min at 200 gpm and 42,092 tank volume and 0.63% baffling factor (from tracer study). ACTION NEEDED: Further investigate cause and extent of the treatment implications.
 
Associated Alerts: N/A - -



More information for this water system: SDWIS ID 3926
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login