OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrick Yates (503) 665-9320
Contact Date: 05/30/2013
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SOCs
N/A
 
Details: SUMMARY: Response to Di-2 ethyl hexyl phthalate detect well #8 DETAILS: I spoke to Derrick about the 10/31/11 detect of this chemical at 0.00065 mg/L, slightly above the detection limit of 0.0006 mg/L, but less than the MCL of 0.006 mg/L. System to begin quarterly monitoring for individual chemical 7/1/13 due to initial detect greater than the detection limit per OAR 333-061-0036 (3)(a)(C ). DWS to review results after two quarters of monitoring (in January 2014) to re-evaluate any potential follow up detections and see if any monitoring reductions are warranted. We discussed some potential sources of this chemical such as electrical tape used for wellhead equipment. ACTION NEEDED: DWS to offer support to the City to follow up initial detection.
 
Associated Alerts: CHEM5784 - 05/29/2013 - DI(2-ETHYLHEXYL) PHTHALATE



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3298