OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00295
PWS Name: BIG SPRUCE MHP LLC
 
Who Was Contacted and Phone: Kevin Hunt
Contact Date: 07/11/2013
Contacted By: PULS, SARAH (LANE COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY COMPLAINT
Reasons: Chlorine
N/A
 
Details: SUMMARY: Complaint of high chlorine and brown water DETAILS: A tenant at the MHP called and complained that the water at the facility had high chlorine and was brown in color. Complainant also said that the property has new owners and that he thought that since the new owners took over no one was running the water system. Complainant also said that in February well drillers were out there doing work on the water system.I called the new owners, Debbie Keating (already updated on SDWIS) and spoke with her she said Delta Environmental was hired to be the certified operator onsite. Kevin Hunt with Delta went out the site this week and did a walk through. The onsite manager who will be under the direction of Kevin Hunt was not properly managing the chlorine levels and the pH for the corrosion control. Chlorine onsite was 1.2 ppm and pH was 7.0, Kevin adjusted the chlorine down and the pH up to bring the levels back to a more appropriate range. Kevin is going to meet with Christensen Well Drilling to confirm what work they did back in February at the site, but Kevin was told by a tenant onsite that the well drillers reconditioned some of the wells onsite to get more gpm. ACTION NEEDED: Kevin will follow up with me after talking with Christensen Well Drilling to make sure the work they did in February does not need to go through plan review.


More information for this water system: SDWIS ID 3297
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login