OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00217
PWS Name: LAUREL ACRES WATER CO INC
 
Who Was Contacted and Phone: Leo Jones (503) 969-4415
Contact Date: 02/19/2014
Contacted By: FEDERICO, JOSEPH (WASHINGTON COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Positive Ecoli DETAILS: I contacted Gregg Baird and asked if the system needed to do source testing or just 4 repeats in distribution. Gregg checked and left message that they only need to do the 4 repeats no source test. I contacted Leo and asked what happened. Eh said there was air in the chlorinator line which he fixed. He said yesterdays test was over 0.20ppm at his home. He usually maintains 0.30. He immediately checked the chlorinator today when he tested 0.10 at the home. He said the lab took the sample upstream and noted 0.00ppm. He thinks they still had residual in the system the entire time but not a min of 0.20ppm He issued a boil water notice to all users already., He will take 4 repeats as soon as possible in the distribution. He tested the residual in his home 1 hour ago and had 0.30ppm. Leo will keep boil notice in place until test results come back ok. I spoke to Gregg and discussed incident. I contacted Leo and he said he is picking up the sample bottles today and will have samples in to the lab by tomorrow morning. I reminded Leo minimum residual is 0.30ppm for chlorine ACTION NEEDED: none
 
Associated Alerts: COLI12623 - 02/19/2014 - COLIFORM (TCR) , E. COLI

COLI12623 - 02/19/2014 - COLIFORM (TCR) , E. COLI



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3272