OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05737
PWS Name: BERNDT CREEK WATER CORP
 
Who Was Contacted and Phone: Martin Van Dyken (503) 410-1160
Contact Date: 09/25/2014
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
SWTR
 
Details: SUMMARY: Follow up on toluene detect and update on on-line NTU meter DETAILS: Martin and I discussed the 9/3/14 0.0009 mg/L detect for toluene that was above the 0.0005 detection limit of 0.0005 mg/L, but less than the MCL of 1 mg/L. We discussed that since this value was in the range of the earlier detects when the system monitored quarterly, that the system would continue to monitor toluene annually with the VOC suite during 3rd quarter, the quarter that yielded the highest result. Martin also updated me that the on-line 1720E meter has been installed right after the filter and the electrical work is done. The drain to collect the water right after the filter and the valve to return water from the meter to the plant is getting completed, hopefully within a week. HACH will then come out to inspect and set up the instrumentation to begin using the meter. Martin will then call me when the meter is on-line and being used for compliance NTU readings every 4 hours of plant operation. ACTION NEEDED: Martin to contact DWS upon on-line meter up and running. DWS to conduct water system survey at that time, during 2014 calendar year.
 
Associated Alerts: CHEM6440 - 09/24/2014 - TOLUENE



More information for this water system: SDWIS ID 2056
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login