OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrick Yates (503) 969-6449
Contact Date: 03/25/2015
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: Follow up on PCE detect well #5 DETAILS: Spoke to Derrick about 0.002 mg/L detect of tetrachloroethylene (PCE) from 3/11/15 sample from the entry point of well #5 and #9, with well #5 contributing exclusively to the sample. Sample result is in range of previous detects, while above detection limit of 0.0005 mg/L, is below MCL of 0.005 mg/L. City is researching potential causes of chemical seen in well #5. City uses #5 occasionally, generally once a week, to keep the well exercised and to meet peak demands. ACTION NEEDED: City to continue once annual sampling during first quarter at the entry point with well #5 only contributing to the sample, with the next sample due in 2016. DWS to support City in researching potential source of contaminant.
 
Associated Alerts: CHEM6669 - 03/25/2015 - TETRACHLOROETHYLENE



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3298