PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrick Yates (503) 969-6449
Contact Date: 03/25/2015
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: VOCs
N/A
 
Details: SUMMARY: Follow up on PCE detect well #5 DETAILS: Spoke to Derrick about 0.002 mg/L detect of tetrachloroethylene (PCE) from 3/11/15 sample from the entry point of well #5 and #9, with well #5 contributing exclusively to the sample. Sample result is in range of previous detects, while above detection limit of 0.0005 mg/L, is below MCL of 0.005 mg/L. City is researching potential causes of chemical seen in well #5. City uses #5 occasionally, generally once a week, to keep the well exercised and to meet peak demands. ACTION NEEDED: City to continue once annual sampling during first quarter at the entry point with well #5 only contributing to the sample, with the next sample due in 2016. DWS to support City in researching potential source of contaminant.
 
Associated Alerts: CHEM6669 - 03/25/2015 - TETRACHLOROETHYLENE



More information for this water system: SDWIS ID 3298
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login