OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95236
PWS Name: BELLINGER PRODUCE LLC
 
Who Was Contacted and Phone: Jack Bellinger
Contact Date: 06/11/2015
Contacted By: SCHWAB, SARAH (DEPT OF AGRICULTURE)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Total Coliform postive-- sample date 6/08/2015. DETAILS: Routine sample for Total Coliform resulted in positive. Maintenance work was completed on existing well. Sample site was at store room sink. Went over how to eliminate coliforms from well. Four repeat samples must be collected within 24 hours. ACTION NEEDED: When a routine sample is total coliform-positive, a set of repeat samples must be collected within 24 hours of being notified of the positive results by the certified laboratory. Systems which collect one routine sample/month or less must collectat least four repeat samples for each total coliform-positive samplefound. The system must collect at least one repeat sample from the sampling tapwhere the original total coliform-positive sample was taken, and at least one repeat sample at a tap within five service connections upstream and at least one repeat sample at a tap within five service connections downstream of the original sampling site. All repeat samples must be collected on the same day. Additionally, the firm must collect five routine samples the month following the routine present sample regardless of whether an MCL violation occurred or if repeat sampling was absent.
 
Associated Alerts: COLI14223 - 06/11/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4855
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login