OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01092
PWS Name: USFS TILLER RANGER STATION
 
Who Was Contacted and Phone: John Beagle
Contact Date: 03/11/2016
Contacted By: TEMPLIN, REBECCA (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
Lead/Copper
 
Details: SUMMARY: Lead Exceedance from samples taken 7/8/2014 DETAILS: Lead samples from 7/8/2014 showed the 90% lead result was 0.0180 mg/L (action level = 0.0155 mg/L). Wrote a letter to the system explaining the increase of lead and copper sampling to 10 samples every 6 months and requirements of taking water quality parameters. ACTION NEEDED: Take 10 lead and copper samples prior to 6/30/2016.
 
Associated Alerts: chem7075 - 03/15/2016 - LEAD 90TH % VALUE