OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 92040
PWS Name: EDDYVILLE CHARTER SCHOOL
 
Who Was Contacted and Phone: Jennifer Johnson (541) 875-0452
Contact Date: 12/12/2016
Contacted By: CHAPMAN, AMY (LINCOLN COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: 2 out of 10 Samples Taken 10/26/2016 Exceeded the MCL for Lead DETAILS: Sent email to Jennifer Johnson.With regard to Lead and Copper need to start measuring pH, sending in the pH reports and issuing public education. Following are some details.1. Water systems using corrosion control are required to measure and record pH at the entry point and a distribution point. Attached are two forms: one to record the pH at the entry point and one to record pH at the distribution point farthest from the well.Measure and record pH at 2 different sampling places:Entry point (before 1st user) at least once every 14 days-- send in monthly. Recommend measuring more often, like daily, because when the pH is below 7.2 every day, there is no record-- it is assumed the pH was out of compliance. Violations are issued for how many days the pH was out of compliance. Distribution point (1 sample point the farthest from the well) once 6 months apart-- send report in every 6 months.2. Reissue Public Education for lead and copper in schools.3. There will be a letter about lead and copper compliance to clarify what needs to be done by when. ACTION NEEDED: None.
 
Associated Alerts: CHEM7399 - 11/18/2016 - LEAD SUMMARY



More information for this water system: SDWIS ID 1133
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login