OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00205
PWS Name: COOS BAY NORTH BEND WTR BRD
 
Who Was Contacted and Phone: Jerre Cover (541) 267-3128
Contact Date: 02/13/2017
Contacted By: PARRY, BETSY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
None
 
Details: SUMMARY: One filter turbidity spike DETAILS: Jerre Cover contacted me to let me know that Filter 4 had an unusual short-term turbidity spike on Sunday - peak was 1.84 NTU, and the level was over 1.0 for approx. 2 minutes. It was not at a time the filter was due to be washed, nor did the water look dirty when they baskwashed immediately afterwards. Jerre had never seen a quick increase like this in his 5 years there. Their best guess is that some gunk broke loose in the plumbing enroute to this turbidimeter. CBNB uses the highest IFE instead of CFE for compliance because the pump location in relation to their CFE line may distort the readings. Even so, good to note that there was no perceptible change in the recorded CFE levels during this time. Using the highest IFE in this event, there does not seem to be a treatment technique violation because the > 1 NTU occurrence was not one of the required 4-hour readings. ACTION NEEDED: None from a compliance stand point. Good that the operator reported the issue. May send more guidance on the compliance triggers for IFEs and CFEs.


More information for this water system: SDWIS ID 3881
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login